Rooftop units: advantages, installation times, and applications for large spaces

In brief

A rooftop unit is a packaged system, typically installed on a building’s roof, that combines air conditioning, heating and air renewal. It is self-contained and tested at the factory: no heating plant, no hydronic circuits and no additional control systems. A single lift, ductwork connections and commissioning. It is the ideal choice for comfort applications, production areas or general storage spaces.

Anyone designing the HVAC system for a shopping centre, a logistics hub or a multiplex cinema faces the same choice. One option is a conventional hydronic system: a heating plant, chillers, a pipework network, air handling units and terminal units. The other moves everything onto the roof and reduces the work on site to just a few operations.

The first question is almost always about timing. And it is the right question, because for a retail space or a warehouse, the real cost is not just the system itself: it is every week the building cannot open.

Clivet rooftop unit installed on a roof. Compact apparatus for climate control and air renewal.
What is a rooftop unit?

A rooftop unit is a self-contained system installed on the roof of a building. It houses all the components needed to control the indoor climate in a single casing: a refrigeration circuit, fans, a filtration section, a heat recovery unit and a control system.

The European technical reference guide published by Eurovent defines rooftop units as compact, self-contained systems that incorporate all the components required for efficient air renewal and indoor thermal comfort control.

This is the key difference from an air handling unit (AHU): an AHU conditions the air but relies on external heating and cooling sources, whereas a rooftop unit generates its own heating and cooling and delivers them directly to the air.

The result is that a single unit performs three functions that would otherwise require three separate systems:

  • summer cooling, with the refrigeration circuit cooling and dehumidifying the air;
  • winter heating, in heat pump mode, without combustion or the need for a flue;
  • air renewal, with adjustable outdoor airflow and filtration.
  • energy recovery from exhaust air

However, a fundamental distinction must be made from the outset: conventional hydronic systems remain necessary for all applications where environmental conditions must be controlled to strict specifications (e.g. cleanrooms, industrial processes, food storage, data centres). On the other hand, rooftop units offer better performance in comfort applications, in production areas or in warehouses used for general storage.

The advantages of a rooftop solution

One unit, three functions

The most immediate benefit is simpler management: one supplier, one maintenance contract and one point of contact in the event of a fault. A single unit replaces what would otherwise be a boiler, a chiller and an air handling unit, each with its own service life and inspection requirements.

No intermediate conversion losses

In a hydronic system, energy passes through several stages: the heat source heats the water, the water flows through the pipework, and a heat exchanger transfers that heat to the air. Each stage involves a loss. A rooftop unit has an integrated refrigeration circuit and directly heats or cools the air being treated, eliminating the intermediate stages.

Free-cooling: cooling without running the compressors

When outdoor air is cooler than indoor air, such as in spring and autumn, at night or in the early morning, the rooftop unit increases the outdoor airflow and cools the building without running the compressors.
There are two control strategies:

  • temperature-based free-cooling, which considers only the outdoor temperature;
  • enthalpy-based free cooling, which considers both temperature and humidity and is therefore more suitable for humid climates, such as those found across much of Italy's lowland areas.

In a building with high internal heat loads from lighting, occupants and equipment, free cooling operates for a significant part of the year.

Heat recovery

Exhaust air carries energy that has already been paid for. Heat recovery captures this energy before it leaves the building and can be achieved thermodynamically, by directing the exhaust air towards the outdoor heat exchanger, or by using a passive heat recovery unit. In winter, heat recovery provides an additional benefit: it reduces the frequency and duration of defrost cycles.

Clivet rooftop units use the patented REVO energy recovery system (short for Recovery EVOlution), an advanced thermodynamic technology developed by Clivet specifically for its industrial and commercial air conditioning and air treatment systems. An ideal solution for maximum energy savings in large commercial spaces, it reduces electricity consumption by using thermal energy that would otherwise be lost outdoors.

Continuous capacity modulation to match the actual thermal load

Full inverter technology, or multiscroll technology for units with higher capacities, makes it possible to optimise energy consumption by adjusting the system output to the actual thermal load at any given moment. This avoids running the system continuously at 100% capacity and ensures that its output closely matches the actual load in the space.

Variable airflow

Modulating the airflow instead of keeping it constant has a major impact on energy consumption: fans account for a significant share of a rooftop unit's overall energy demand, and the documented reduction in consumption achieved with variable airflow is around 30%.
Unlike the compressors, which operate only in response to actual thermal loads, the fans remain operational throughout the year, including during free cooling. Since the compressors operate for only 60-80% of the fans' running time, introducing fan modulation is a key strategic measure. Adjusting fan airflow enables further substantial savings in overall electricity consumption.

Indoor air quality

A rooftop unit does more than control the temperature: it supplies filtered outdoor air. In spaces with a high density of occupants, this factor has a greater influence on perceived comfort than temperature itself. The latest filtration sections achieve high efficiency classes under ISO 16890, capturing fine particulate matter, pollen and pollutants.

Clivet rooftop units can also adjust the outdoor air supply according to actual occupancy levels (based on CO2 measurements), avoiding unnecessary energy use by treating outdoor air only when it is needed.

Maintenance on the roof

All maintenance work takes place on the roof, without accessing areas open to the public. In a shopping centre or cinema, this means the system can be maintained during opening hours, without closures or having to set up work areas on the sales floor.

Learn more about Rooftop

Where rooftop units make a difference

Rooftop HVAC system on a commercial center roof. Modular solution for retail climate control.
Shopping centers and retail

This is the application the technology was originally developed for. A shopping centre experiences large variations in thermal loads throughout the day, driven by visitor numbers, lighting, shop windows and glazed surfaces, and requires ventilation airflow matched to occupancy levels.

Modularity is the key strength: separate units can serve different areas of the mall, each with its own controls. Each store maintains its own comfort profile, and future expansion can be achieved by adding a unit rather than resizing a central plant.

Cinemas and theaters

Here, the focus is on peaks in occupancy: an auditorium can go from empty to full in ten minutes, and people bring both heat and carbon dioxide. The rooftop unit responds on two fronts at once, adjusting both its thermal output and fresh air ventilation to actual occupancy levels.

In these venues, another requirement is just as essential as comfort: quiet operation. Locating the unit on the roof moves the noise source away from the auditorium.

Interior of Amilcare Ponchielli Theater. Clivet rooftop for acoustic comfort and air renewal.
Logistics warehouse interior. Rooftop systems for humidity control and air volume management.
Warehouses and logistics hubs

This segment deserves a closer look, because rooftop units are used less widely here than they should be, and the requirements are more specific.
A warehouse is not simply a larger office. It has its own characteristics that completely change the system design:

  • Very large internal volumes and low occupancy. There is no need for the continuous air exchange required in a crowded space: the large internal volume combined with low occupancy means a much lower ventilation rate is sufficient.
  • Humidity is the real enemy. In a warehouse, humidity control is critical to prevent damage to goods. Condensation on packaging, corrosion, mould, deterioration of paper and cardboard, and risks to electronic components: these are direct costs, not comfort issues.
  • High ceilings and stratification. Warm air rises and accumulates beneath the roof, where it serves no useful purpose. The air distribution system must be designed to counteract stratification, rather than suffer its effects.
  • Regulatory requirements for the microclimate. Italian Legislative Decree 81/2008 includes the microclimate among the risk factors to be evaluated in the risk assessment document and requires temperature, ventilation and humidity to be appropriate for the activities carried out. For moderate thermal environments, UNI EN ISO 7730 indicates a relative humidity of between 40% and 60%.

There is also a factor that changes the economics of the project: logistics warehouses have large roof areas with structural provisions in place, often already intended to accommodate photovoltaic systems. There is already space for rooftop units, without taking up usable storage space, a warehouse's most valuable resource.

Rooftop units for kitchens:

always fresh air with the FFA (Full Fresh Air) system

Commercial kitchens, such as those in fast food restaurants, are particularly demanding environments for climate control. Griddles, fryers and ovens produce large amounts of heat and moisture, while extractor hoods continuously remove air, fumes and odours generated during food preparation.
To maintain comfortable working conditions and ensure adequate air exchange, a rooftop unit using 100% outdoor air (FFA - Full Fresh Air) can be used. This system treats and supplies only air drawn from outside.
Unlike conventional air conditioning systems, this solution does not reuse indoor air, preventing cooking odours and particles from being recirculated. The outdoor air is filtered and heated or cooled before being distributed throughout the kitchen.
Another key aspect is airflow balancing. The FFA rooftop unit supplies fresh air to replace the air removed by the extractor hoods, helping to maintain the correct pressure relationships between different spaces. Precise control therefore helps limit the spread of odours to the dining area and other parts of the restaurant.
The system also manages the temperature variations typical of commercial kitchens by supplying conditioned air. This means that even when the equipment is operating at full capacity, staff can work in a comfortable environment, without unpleasant draughts or excessive temperature fluctuations.

Detail of a Clivet rooftop unit. HVAC system for large areas.
Clivet rooftop installed outdoors. Comfort and air management in dining rooms, with free cooling function.
Rooftop units for dining areas:
tailored comfort for every guest

In dining areas, air conditioning requirements are very different from those of kitchens. Here, temperature and air quality depend mainly on the number of people present, which can change rapidly throughout the day, and on heat transfer through glazed surfaces.
To meet these needs, the rooftop unit serving the dining area can combine outdoor air with recirculated air, adjusting the system's operation to ensure the right level of comfort while limiting energy consumption.
One of the most interesting features is free cooling, which makes direct use of outdoor air when its temperature is favourable. Under these conditions, the system can cool the spaces without relying on normal compressor operation, significantly reducing the energy required for air conditioning.
Fresh air ventilation can also adapt to the dining area's actual needs. Dedicated sensors measure CO₂ concentration, allowing the system to increase or decrease the amount of outdoor air supplied according to occupancy. This ensures greater air exchange when the restaurant is full, while avoiding unnecessary energy use during quieter periods.
Another benefit concerns the separation between the kitchen and the dining area. With proper pressure control, the dining area can be maintained at a slightly higher pressure than the kitchen, creating an airflow that helps limit the spread of cooking odours towards the tables.
The result is a pleasant, comfortable environment for guests, with a more even temperature, continuous air renewal and more efficient energy management, even during the busiest periods.

How long does it take to install the HVAC system of a shopping center with rooftop units

An honest answer cannot be reduced to a fixed number of days: it depends on the size of the building, the number of units and how the site work is organised. But a precise answer is possible, because the advantage of a rooftop unit is not that it completes the same tasks faster: it eliminates some of them altogether.

Here is the comparison, stage by stage.

Construction stage Conventional hydronic system Rooftop system
Plant room Needs to be built: space, structural work, access, ventilation Not required
Heat generation Boiler, flue, fire safety documentation, gas connection (an outdated practice in new buildings) Integrated into the unit
Cooling generation Chiller, mounting base, connections Integrated into the unit
Hydronic circuits Pipework, insulation, pumps, expansion vessels, manifolds None
Refrigerant charging Already completed at the factory Already completed at the factory
Component testing On site, component by component Already completed by the manufacturer
Unit positioning Installation on the roof A single lift from the truck to the roof
Connections Air ductwork + a separate power supply for each component installed on site Air ductwork + a single power supply for the entire system
Commissioning Hydronic balancing, calibration of multiple subsystems, supervisory control, definition of control logic Setting the controller parameters

Rooftop units are assembled at the factory and inspected by the manufacturer: they arrive on site as finished products, not as a set of components to be assembled.

4 practical implications for the construction schedule:

  1. Tasks run in parallel instead of one after another. With no need to wait for the heating plant to be built, the HVAC installation no longer holds up other work: it proceeds alongside the interior finishing work.
  2. There is less work inside the building. Almost the entire system is located on the roof. For work on existing buildings, such as refurbishment, a change of use or the expansion of a retail space, this means drastically reducing disruption to areas that need to remain operational.
  3. There are fewer variables on site. Having fewer components to connect on site means fewer unexpected issues and a construction schedule that stays on track.
  4. A single point of contact. Traditional systems may involve a different supplier for each component (AHU, chiller, heat pump), whereas with rooftop systems, a single supplier is responsible for the entire system.

Clivet rooftop units: Italian leader and among the top 5 in Europe

Clivet maintains a strong presence in the rooftop segment with one of the most extensive ranges available on the Italian market, featuring capacities starting from approximately 25 kW up to 343 kW, covering all sizes from small retail spaces to logistics hubs.

AscProducts Image

Patented REVO (Recovery EVOlution) thermodynamic recovery

AscProducts Image

Full inverter technology extended up to 160 kW

AscProducts Image

IEQ (indoor environmental quality) also guaranteed by iFD filters

Some distinctive features of the range:

  1. Full inverter technology available on units up to 160 kW, with modulation of both compressors and fans. This enables the unit to operate at part load for most of the season, reflecting real operating conditions.
  2. REVO (Recovery Evolution), the patented thermodynamic heat recovery system that uses a dedicated fan section to recover energy from exhaust air, improving the unit's overall efficiency.
  3. R32 refrigerant (GWP 675, with a refrigerant charge that is on average 40% lower than for R410A) and R454C (GWP 148). R454C's GWP below the threshold of 150 enables compliance with the most stringent deadlines set out in Regulation (EU) 2024/573 (F-Gas).
  4. Specially sized ranges to meet the specific requirements of different applications (medium occupancy, high occupancy, 100% outdoor air).
  5. Seasonal efficiencies among the highest in the segment, with declared SEER and SCOP values 30% above ErP requirements.
  6. Extended operating range, from −15 °C in heating mode to +48 °C in cooling mode.
  7. iFD filtration using electrostatic technology, up to class ePM1 90% under ISO 16890, with the option of integrating germicidal UV-C lamps.


The cooling performance of units up to 200 kW is certified by Eurovent.

Discover the Clivet Rooftop range

Frequently asked questions about rooftop units

There is no one-size-fits-all answer for every site, but rooftop units eliminate entire stages of the process compared to a traditional system: there is no need for a plant room, no need for a boiler room, there are no hydraulic circuits to install and insulate, and the control logic integrated into the unit itself makes it fully plug-and-play, autonomously managing temperature control, air flow rates and operating parameters without requiring complex automation wiring on site.

All that remains is hoisting it onto the roof, connecting it to the ductwork and the mains electricity supply, and commissioning it. Furthermore, the installation of the system no longer acts as a constraint on other works, as it can proceed in parallel.

An air handling unit treats and circulates air, but to heat or cool it, it requires external heat exchangers, typically air-conditioning systems and a refrigeration unit. A rooftop unit integrates the refrigeration circuit within itself and directly heats or cools the treated air, without separate heat exchangers or hydraulic circuits.

 

Yes. Reversible rooftop units operate as heat pumps and cover the entire heating season. The latest-generation units operate at external temperatures as low as −15 °C, without combustion, a flue or a gas connection.

Rooftop units are perfect for applications in medium- to large-sized buildings characterised by variable load and occupancy profiles, where temperature and humidity setpoints are applied to ensure human comfort. Examples include shopping centres, manufacturing and logistics hubs, restaurants, cinemas, auditoriums and sports halls.

Yes, and this is an application where they offer specific advantages. Large spaces with limited occupancy do not require the continuous air exchange needed in a crowded environment, whilst humidity control is critical for preserving goods. The roof of a warehouse, which is already spacious and structurally suitable, accommodates the units without taking up any storage space.

It is the mode in which the unit cools by increasing the flow of outside air – when this is cooler than the indoor air – without running the compressors. Control can be thermal, based solely on temperature, or enthalpic, based on both temperature and humidity, and is therefore more effective in humid climates. The savings depend on the climate and the building’s internal loads: the greater the difference between the internal and external temperatures, the greater the savings.

The unit is located on the roof, so the noise source is, by design, distant from occupied spaces. In applications with stringent acoustic requirements, such as cinemas and theatres, the design must nevertheless include anti-vibration mounts and correctly dimensioned ductwork, as these are the main routes through which noise is transmitted into the building.

It depends on the size of the units and the number required. The first design parameter to check is not so much the overall dimensions as the structural load-bearing capacity of the roof and the clear technical space around each unit for air ducts and maintenance. In logistics warehouses and shopping centres, the available space is normally ample.

Designing systems with heat recovery

Designing systems with heat recovery

Recovery can be achieved with different product technologies (multifunction units, VRF systems, rooftop units and zephir units). Each technology offers a different type of recovery.

business, VMC, heat recovery, VRF, rooftop
HOTEL rooms

Air conditioning in hotels: Hydronic, VRF, WLHP or Rooftop?

Hotels provide very different environments, but they are united by the need to ensure optimal comfort for guests.